Certifications and compliances
Application in Zone 2 area acc. IEC 60079-15
- Marking to 94/9/EC: Ex II 3 G Ex nR II T*...Gc
- EC - Type Examination: LCIE 09 ATEX 1002
Application in Zone 21 and 22 areas acc. IEC 61241-1
- Marking to 94/9/EC: Ex II 2 D Ex t IIIC T...°C(*) Db IP66
- EC - Type Examination: LCIE 09 ATEX 3008
General per both application Zone 2 and 21
- Temperature ambient of use: -45°C to +55°C
- Electromagnetic compatibility: EN 61000-6-4
- Degree of protection: acc. EN 60529 IP66