Certifications and compliances

NEC:

EYD11-EYD101, EYD116-EYD1016

  • Class I, Divisions 1 & 2, Groups B, C, D
  • Class II, Division 1, Groups E, F, G
  • Class II, Division 2, Groups F, G
  • Class III

EYD1-EYD10, EYD16-EYD106, EZD111-EZD611

  • Class I, Divisions 1 & 2, Groups C, D
  • Class II, Divisions 1 & 2, Groups F, G
  • Class III

UL standard:

  • UL1203

CSA standard:

  • C22.2

Design features

EYD and EZD drain sealing fittings include:

  • Drain to provide continuous, automatic drainage of condensate
  • Large openings with threaded closures to provide easy access to conduit hubs for making dams
  • Integral bushings to protect conductor insulation from damage
  • Taper tapped hubs to ensure ground continuity

EZD drain and inspection sealing fittings also include:

  • Removable covers for periodic inspection of seals
  • Barrier for sealing compound easily installed after dams are made and before compound is poured

Standard materials

  • Bodies and inspection or drain covers – Feraloy iron alloy and/or ductile iron
  • Closure for drain – copper-free aluminum or ductile iron
  • Small closure plug – Feraloy iron alloy and/or steel
  • Drain – stainless steel
  • Removable nipples – steel